        <article-title>输电线路杆塔基础在冻融循环作用下的承载能力衰减机理及加固技术</article-title>
      </title-group>
      <contrib-group>
        <contrib contrib-type="author">
          <string-name>王涛</string-name>
        </contrib>
        <contrib contrib-type="author">
          <string-name>王晓旭 鄂尔多斯供电公司输电管理二处</string-name>
        </contrib>
      </contrib-group>
      <pub-date pub-type="epub">
        <year>2025</year>
        <month>10</month>
      </pub-date>
      <issue>10</issue>
      <abstract>
        <p>为解决冻融循环导致输电线路杆塔基础承载能力衰减的工程问题，本文从机理分析、调研试验及加固技术三方面展开研究。揭示了承载能力衰减的“土体劣化-界面失效-材料损伤”多因素耦合机理，明确该过程分初始、加速、失稳三阶段，且土体劣化影响最为显著。其次通过东北、西北冻土区126基杆塔基础现场调研，发现埋深浅的掏挖式/板式基础变形最突出，服役超10年基础混凝土损伤率达85%，并结合室内多尺度试验，验证细粒土力学性能劣化、基础-土体界面黏结衰减及混凝土抗拉强度损失的规律。针对现有加固技术“系统性不足、耐久性差”的局限，提出微生物矿化土体改良、长短桩+土工格栅复合支护、抗冻混凝土+一体化防护层三类新型技术。通过数值模拟验证了其在控制位移、提升承载力和抑制损伤方面的优越性，明确了各自的适用边界，研究成果为冻融区输电线路杆塔基础的安全运维与加固设计提供了理论支撑和技术参考。</p>