      <abstract>
        <p>电能计量专用电压、电流互感器或专用二次绕组及其二次回路不得接入与电能计量无关的设备。本文以主变关口电能表电流回路
变更为背景，对 3/2 接线的升压站变送器电流回路接线变更过程进行了详细阐述，对改造后 CT 极性的验证进行了重点描述，通过一种实
际、可行的方法验证了 CT 回路变更后极性的正确性，这种方法在实际工作应用中具有一定的借鉴意义。
关键词：主变关口电能表；电流回路变更；3/2 接线；CT 极性验证</p>