      <abstract>
        <p>超高层建筑施工临时消防给水系统由于垂直高差大、管线长、启停频繁，水锤瞬变压力峰值达到 8～12MPa，远远超过常规镀锌钢
管的承压能力，已多次发生立管爆裂、阀件击碎、核心筒大面积淹没等恶性事故。本文以上海中心大厦（632m）、广州东塔（530m）、深圳
平安金融中心（599m）、天津周大福金融中心（530m）、武汉绿地中心（606m）等十余个 600m 级超高层项目三年以上的跟踪实测数据为基
础，系统揭示了施工期瞬变压力的产生机理、传播规律和破坏模式，首次提出了“分区恒压供水+空气罐-液控缓闭蝶阀-微阻缓闭止回阀
三级组合防护+高频压力实时监测预警”的成套技术体系。在武汉绿地中心 F103 层以上区域实测，该体系把最恶劣工况下的水锤峰值从
8.7MPa 降到 2.3MPa 以下，降幅达 73.6%，负压区消失，系统安全、稳定。为同类型工程提供可以复制、可以量化的技术路径。
关键词：超高层建筑；施工临时消防；水锤；瞬变压力；液控缓闭蝶阀</p>