      <abstract>
        <p>为了研究生活垃圾焚烧厂冷却塔在恶劣环境下腐蚀问题，本文以某焚烧发电厂冷却塔为工程案例，通过现场腐蚀调查与检测、水
质和大气环境数据分析，对冷却塔的腐蚀特征及原因进行了系统的研究。结果显示，高浓度氯离子侵蚀、酸性气体化学腐蚀是造成混凝土
中性化、钢筋锈蚀和结构劣化的主要原因。在此基础上提出以材料体系优化、阴极保护设计、运行参数调节为内容的综合治理措施，为焚
烧厂冷却塔耐久性设计和运维管理提供技术上的参考。
关键词：生活垃圾焚烧厂；冷却塔；氯离子侵蚀；混凝土劣化</p>