<?xml version="1.0" encoding="UTF-8"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD JATS (Z39.96) Article Authoring DTD v1.4 20240229//EN" "JATS-articleauthoring1.dtd">
<article article-type="research-article" xml:lang="zh-CN" xmlns:xlink="http://www.w3.org/1999/xlink">
  <front>
    <journal-meta>
      <journal-id journal-id-type="publisher-id">29</journal-id>
      <journal-title-group>
        <journal-title>《建筑施工与发展》</journal-title>
        <abbrev-journal-title>CONSTRUCTION AND DEVEL OPMENT</abbrev-journal-title>
      </journal-title-group>
      <issn>ISSN：2737-4262；EISSN:2705-1269</issn>
      <publisher>
        <publisher-name>华文科学出版社</publisher-name>
      </publisher>
    </journal-meta>
    <article-meta>
      <article-id pub-id-type="doi">10.12421/JZSGYFZ2705-1269-0803061</article-id>
      <article-id pub-id-type="publisher-id">27432</article-id>
      <title-group>
        <article-title>脱硫MGGH 系统耗水量优化研究</article-title>
      </title-group>
      <contrib-group>
        <contrib contrib-type="author">
          <string-name>吴 玮 康冰译 王光超 丁 燕 上海电力能源科技有限公司</string-name>
        </contrib>
      </contrib-group>
      <pub-date pub-type="epub">
        <year>2026</year>
        <month>3</month>
      </pub-date>
      <issue>3</issue>
      <abstract>
        <p>为了解决漕泾电厂脱硫 MGGH 系统耗水量大的问题，提高机组运行的经济性以及环保合规性，本文用 PDCA 循环法，结合现场
实测、数据统计、对标分析、试验验证等方式开展系统的研究。结果表明，在负荷 600MW 以下工况下，循环水系统耗水占比 63.79%是主
要问题，主要原因是由于一级烟气冷却器换热效率低（95%）、一级烟冷蒸汽吹灰压力大（0 .9MPa）；采用更换真空热管换热器（换热效率 99%）、
采声波吹灰器（声压级 160 分贝）等优化措施后，系统周均耗水量从 1170 吨降低到 574 吨，比目标值（675 吨/周）降低 15%，设备氧腐蚀
程度明显降低，烟囱“白色烟羽”排放减少。该方案数据支持充分、实施流程规范，可以给同类型火电机组 MGGH 系统节水改造提供可靠
的技术参考和实践借鉴。
关键词：脱硫 MGGH 系统；耗水量优化；PDCA 循环；真空热管换热器</p>