      <abstract>
        <p>施工期内的供水管网漏损，因管线接口变动频繁、临时供水路径不固定、施工碾压与震动等因素，往往难以通过常规运行监测手
段及时发现和定位。本文提出一种基于分区计量的施工阶段漏损主动控制策略，将 DMA 技术框架前移至工程建设环节。通过在施工区段
及周边管网预先划分独立计量区域，接入临时性或已建成的分区流量监测装置，结合夜间最小流量分析与瞬时流量异常预警，建立施工期
漏损的实时感知与快速响应机制。该策略改变了传统“跑水后再查找”的被动处置模式，使漏损控制与施工过程同步开展，可在不中断施
工进度的前提下有效压缩漏水持续时间，降低临时抢修频次。实际工程中可依据施工扰动范围灵活调整分区边界与监测频次，为旧网改造、
管线迁改等施工场景提供可操作的漏损管理路径。
关键词：施工期漏损；分区计量；主动控制；夜间最小流量；施工扰动</p>