<?xml version="1.0" encoding="UTF-8"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD JATS (Z39.96) Article Authoring DTD v1.4 20240229//EN" "JATS-articleauthoring1.dtd">
<article article-type="research-article" xml:lang="zh-CN" xmlns:xlink="http://www.w3.org/1999/xlink">
  <front>
    <journal-meta>
      <journal-id journal-id-type="publisher-id">8</journal-id>
      <journal-title-group>
        <journal-title>《科技研究》</journal-title>
      </journal-title-group>
      <issn>ISSN:3079-9244（原2717-5480）</issn>
      <publisher>
        <publisher-name>华文科学出版社</publisher-name>
      </publisher>
    </journal-meta>
    <article-meta>
      <article-id pub-id-type="doi">10.12421/kjyj3079-9244-2026-4-65</article-id>
      <article-id pub-id-type="publisher-id">27543</article-id>
      <title-group>
        <article-title>基于 PLC 控制的 STS 双电源静态开关在中波发射台供配电系统中的应用方案</article-title>
      </title-group>
      <contrib-group>
        <contrib contrib-type="author">
          <string-name>王军 （云南省广播电视局马关中波台 云南马关 663700）</string-name>
        </contrib>
      </contrib-group>
      <pub-date pub-type="epub">
        <year>2026</year>
        <month>4</month>
      </pub-date>
      <issue>4</issue>
      <abstract>
        <p>本文介绍了笔者所在的中波发射台在经历了因雷击导致 UPS“炸机”造成的惨痛教训后，设计制作并成功投入安全播出供配电系统使用的双电源“无感”切换设备，其核心就是应用双电源静态切换开关（STS）把 UPS 变成系统的备用电源，在市电正常的情况下，UPS 空载待命；一旦外电中断，通过 STS 静态切换开关把 UPS 的输出电源“无感”投入系统供电，当后备发电启动正常供电或外电恢复后 UPS 自动退出供电。因 STS 静态开关的介入使用，使 UPS 只工作在外电中断到备用电源供电的时刻，使发射系统设备实现“零停电”，同时也避免了 UPS 因“长时间、大负荷”工作导致电池加速老化、整流和逆变电路的功率器件（SCR、IGBT）击穿短路导致 UPS 停机等风险，提高系统供电可靠性的同时可以大幅延长 UPS的使用寿命、减少 UPS 的运行维护费用。</p>
      </abstract>
    </article-meta>
  </front>
</article>